The following is the standardized insulation testing process and operating points for waterproof cable laying:
Safe power-off and discharge
Cut off all power sources of the cable and hang and lock it. Use a discharge rod to discharge the conductor and metal sheath continuously for ≥ 2 minutes to eliminate residual charges.
Detect environmental humidity<80%, temperature should be within the range of 5-35 ℃, avoid rainy or high humidity periods
.
Equipment selection and calibration
Wiring specifications
Test the insulation between each core and other parallel grounded core wires in sequence (e.g. test four times for a four core cable);
Shielding layer connected to G terminal to eliminate surface leakage current interference
.
single-core cableConnect the L end to the conductor and the E end to the metal sheath (connect to the grounding wire when there is no sheath)
;
multi-core cable:
Parameter Setting and Measurement
Shake the handle at a constant speed of 120 revolutions per minute and maintain a stable test voltage for 1 minute
;
Record the insulation resistance value (unit: M Ω) at 60 seconds, and synchronously record the value of the high-voltage cable for 15 seconds to calculate the absorption ratio (R60s/R15s)
.