The MODBUS/RTU to Ethernet MODBUS/TCP gateway is mainly used in DCS systems with MODBUS/TCP as the backbone network, or in control systems with MODBUS/PLC; If it is necessary to connect some MODBUS devices (such as motor protector MCC, power meter PCC, frequency converter, I/O, etc.) to the Ethernet system, this product is the best choice

MODBUS gateway configuration software: EMGWConfi
Due to the memory sharing principle used in this product, the configuration software EMGWConfi is required to configure the mapping relationship between MODBUS/RTU and MODBUS/TCP storage areas (Zone 0, Zone 1, Zone 3, Zone 4). At the same time, necessary information such as baud rate, checksum, stop bit, slave station address, and IP address and port number on the network port side should be configured to enable the master station to accurately, quickly, efficiently, and cyclically send messages to the slave stations.
EMGWConfi is a top-level configuration software developed and provided by Beijing Dingshi, with independent intellectual property rights. Download configuration for ETH-485-mRTUX product through Ethernet interface.
| Order model | ETH-485-MRTU2 | ||||||
| Ethernet interface parameters | physical interface | 8-pin RJ45, Adaptive interface mode | |||||
| working mode | When working as a MODBUS/TCP server, connect up to 6 clients for easy debugging; When working as a MODBUS/TCP client, 31 server devices can be connected | ||||||
| Baud rate | 10/100 Mbps, adaptive | ||||||
| data volume | Maximum data size of a single MODBUS/TCP message: 255 (starting from the MODBUS device address byte and including the length of the last byte from FC to DU) | ||||||
| Serial port parameters | physical interface | When working as the main station, two independent MODBUS485 main station interfaces can be connected to a maximum of 31 stations per port without the addition of relays, for a total of 62 stations connected to the two ports. | |||||
| Character format | Data bit: 8; Check bits: odd, even, none; Stop position: 1, 2 | ||||||
| working mode | MODBUS RTU master-slave optional | ||||||
| Baud rate | 2400bps, 4800bps, 9600bps, 19.2Kbps, 38.4Kbps, 57.6Kbps, 115.2Kbps are optional | ||||||
| data volume | Register 0 (output coil): 8096Bits, Register 1 (input coil): 8096Bits, Register 3 (input register): 2000Words, Register 4 (hold register): 2000Words |
||||||
| Operational characteristics | configuration method | Use the dedicated configuration software EMGWConfi to configure and download, and select different software and working modes according to actual needs | |||||
| electrical parameter |
power consumption | Power supply: 24VDC (± 20%), current: 90mA | |||||
| working environment | Working temperature: -20 ℃ to+55 ℃ (for customers with lower temperature requirements, please declare at the time of procurement); Relative humidity at work: 5~95% (no condensation) | ||||||
| Storage and transportation temperature | Transportation and storage: -40 ℃ to+70 ℃; | ||||||
| install | Method: 35mm guide rail; Protection level: IP20; | ||||||
| size | Width (55mm) x Length (120mm) x Thickness (104mm); Weight: Approximately 440g | ||||||
| Product Features | Application scenarios | Mainly used to connect MODBUS/RTU devices to DCS systems with MODBUS/TCP as the backbone network | |||||
ETH-485-MRTU2 configuration software
ETH-485-MRTU2 Product Manual