The Preventive Testing Regulations of the Ministry of Electric Power require regular turns ratio or voltage ratio testing of transformers, including semi-finished and finished products during production, transformers before commissioning, and transformers during operation in the power system. The traditional variable ratio bridge is cumbersome to operate, the readings are not intuitive, necessary conversions are required, and the test results only reflect one phase ratio. Overcoming the shortcomings of traditional variable ratio bridge testing, the three-phase variable ratio testing can be completed in one go, with fast testing speed and high accuracy, greatly improving the efficiency of the experiment. (Shanghai Transformer Ratio Tester Manufacturer)
Performance Characteristics
1. The testing range is wide, up to 10000.
2. Fast testing speed, completing single-phase testing in 10 seconds.
3. 240 * 128 color LCD display screen, with a more intuitive interactive interface.
4. Z-shaped connection transformer test.
5. It has the functions of blind variable ratio testing and group testing.
6. Non power-off clock and date display, data storage function (can store 50 sets of test data).
7. The protection function of high and low voltage reverse connection.
8. Transformer short circuit and turn to turn short circuit protection function.
9. Thermal printer output function, fast and silent.
10. Adopting both AC and DC power supply methods, it can be used on site with or without mains power.
11. Small in size, lightweight, and easy to carry.
technical indicators
1. Range: 0.9 to 10000.
2. Accuracy: 0.1% ± 2 words (below 500);
0.2% ± 2 words (500-2000);
0.3% ± 2 words (2000-4000);
0.5% ± 2 words (over 4000).
3. Resolution: Less than 0.0001.
4. Output voltage: 160V, 10V automatic shifting.
5. Working power supply: AC power supply method - requires external AC power supply AC220V ± 10%, 50HZ.
DC power supply method - no need for external power supply (the instrument comes with a built-in lithium battery pack with battery capacity)
24V/6Ah)。
6. Operating temperature: -20 ℃ to 40 ℃.