Detailed explanation of EOCR-I3MZ protector
Date: 2025-12-26Read: 0

Overview of EOCR-i3MZ

32-bit MCU+True RMS measurement, accuracy ± 1%

Protection functions: overload (OC), underload (UC), phase loss (PL), reverse phase (RP), imbalance (Ub), startup stall (Sc), running stall (JA), leakage (lg)

High frequency component filtering - the function of measuring and removing high-frequency components and pulse noise components of leakage current

Action time characteristics: timed limit, inverse time limit, thermal accumulation inverse time limit

THD total harmonic distortion monitoring: real-time monitoring of three-phase, adjustable alarm threshold

Modbus RTU/RS-485 2400-38 400 bps remote communication

Display: Bar load graph+5-digit seven segment digital tube LED

Three phase current automatic rotation display/manual locking of a certain phase display (manual locking function)

Operation/Fault Records:

• Reasons for tripping and current records of the last 3 faults

Accumulated running time and timeout alarm records

• Limit the number of startup records

Fail Safe mode: independent start stop function (safe mode)

Password protection function: Three digit password to prevent accidental operation; Long term shutdown can restore factory settings

Reset mode: manual, automatic, power-off, remote communication

Structural selection: Terminal T, Bottom hole H, Window W

Three phase/single-phase modeMenu switchable

Compliance and certification: UL, CCC, compliant with EU RoHS

EOCR-i3MZ specification sheet

Basic Information

Manufacturer/Brand

Schneider Electric

Product Range (Series)

EOCRseries

Model Name

EOCR-i3MZ leakage protectionRelay (built-in display, integrated)

place of origin

Yishan Factory, South Korea

General agent in China

Shanghai Hanshi Electric Automation Equipment Co., Ltd

Protection function setting range

Protection setting range

0.5~32 A(inverse time limit/heat accumulation inverse time limit), use external CT for 32A and above
0.5-80 A (timed limit), external CT is used for 80A and above

The external CT current range can be extended to 800 A

Time Setting

Leakage Ig0.03-10 A (timed limit 0.05-10 s)

Overload protection OC: timed limit (0.2-30 seconds); Inverse time limit (1-30 classes)

Underload protection UC: timed limit (0.5-30 seconds)

Phase loss protection PL: 0.5 to 5 seconds (can be set to turn off)

Reverse protection RP: Action time 0.15 seconds

Unbalance protection Ub: action time 1-10 seconds, set range 10-50%

Starting blockage Sc:+0.5 seconds after the start delay (D-Time) ends

Running stall JA: 0.2 to 10 seconds

Start delay D-Time

0–200 s, closable