E-mail
1234065@qq.com
-
Phone
17749779099
-
Address
2392A, 1st Floor, 199 Shiyi Road, Baoshan District, Shanghai
Shanghai Hanshi Electric Automation Equipment Co., Ltd
1234065@qq.com
17749779099
2392A, 1st Floor, 199 Shiyi Road, Baoshan District, Shanghai
EOCR-3E420-4-20 mA analog output type
✓ Built in MCU (microprocessor control)
✓True RMSAccurate measurement of three-phase current, with an overcurrent accuracy of ± 3%
✓Main body range: 05 type 0.5-7 A; 80 type 5-80 A;
After connecting to an external CT, the first dose is 10-800 A, and the second dose is 1 A/5 A, which is optional
✓Protection functions: overload, underload, startup stall, operation stall, phase loss, reverse phase, current imbalance4-20 mA analog output
✓Action characteristics: timed, inverse time, hot inverse time, 0.5 s-120 s/Class 1-30 fully adjustable
✓Online parameter viewing (readable during operation)
✓ 5Digital display+LED bar chart; Automatic cycle display of R/S/T current
✓ Automatic/Electrical/Manual Reset: 0.5 s -20 minute timed automatic reset
✓Accumulated motor running time&alarm, fault cause display and historical storage (3 records)
Power outage without losing the last 3 faults and tripping currents
✓Power down mode N (hold)/R (reset) optional
✓Self diagnostic settings(Fail-Safe)The function can be started and stopped independently
✓ Single phase/three-phase optional, low-frequency detection supports 20-400 Hz frequency converter system
✓35 mm DINrail mounting
✓Penetration and terminal type (T) are optional
protection function
✔ Overcurrent (timed limit: 0.2-120 seconds, inverse time limit: 1... 30 classes)
✔ Low current (0.5... 120 seconds)
✔ Phase loss (0.5-5 seconds)
✔ Reverse (0.1... 0.3 seconds)
✔ Current imbalance (1-10 seconds)
✔ Blocked rotation (after D-Time)
✔ 4-20 mA(Real time motor current; load ≤ 500 Ω)
EOCR-3E420Specification Sheet
Basic Information | |
brand |
Schneider Electric |
Product Series |
EOCR |
place of origin |
South Korea (Yishan Factory) |
Authorized General Agent in China |
Shanghai Hanshi Electric Automation Equipment Co., Ltd |
Product Name |
EOCR-3E420Integrated electronic overcurrent relay |
Application of Relay |
Three phase/single-phase motor protection |
Main functions |
Overload, underload, locked rotor (start/run), phase loss, reverse phase, current imbalance4-20 mA analog output |
protection type |
Overload (In>set value) Under load (In<set value) Blocked rotation during startup (In>2-10 × In) Reverse phase Current imbalance (5-50%) |
Network type/frequency |
AC,50 / 60 Hz |
Current setting range |
05:0.5-7A 80:5-80A When used in combination with an external CT, the 05 type can protect up to 960 A when the current exceeds 80A |
analog output |
4-20 mA |
Electrical/mechanical characteristics | |
operating power supply |
100~240V AC |
Installation Method |
Core through type (35 mm DIN rail) |
Contact configuration |
OLTrip: 1 NC+1 NO (95-96/97-98) |
Rated working voltage [Ue] |
600 V AC, 50-60 Hz (main circuit, UL compliant) 690 V AC, 50-60 Hz (main circuit, compliant with CSA) 690 V AC, 50-60 Hz (main circuit, compliant with IEC 60947-4-1) |
Rated impulse withstand voltage [Uimp] |
6 kV(Complies with IEC 60947-4-1) |
Reset method |
Manual/Electrical/Automatic |
Time Setting |
Overcurrent action time: 0.2-120 seconds (timed) Inverse time curve: 1-30 Class |
display mode |
Bar chart+7-segment LED (real-time display of three-phase current and fault codes) |
Relay power consumption |
5 W |
Wiring specifications |
Control circuit cable 2 × 1... 1.5 mm ² flexible wire with cold pressed end (M3 screw) Control circuit cable 2 × 1... 1.5 mm ² flexible wire, without cold pressed end |
Tightening torque |
Control circuit terminal: 0.8-1.2 N · m (suitable for 4.7 mm cables) |
Dimensions (W × H × D) |
Penetrating type: 70 × 56.3 × 106 mm Terminal type: 70 × 91.3 × 106 mm |
Product weight |
Penetrating type: 0.27 kg Terminal type: 0.44 kg |
Last Article: Detailed explanation of EOCR-I3MZ protector