Welcome Customer !

Membership

Help

Shanghai Hanshi Electric Automation Equipment Co., Ltd
Custom manufacturer

Main Products:

smart-city-site>Article

Shanghai Hanshi Electric Automation Equipment Co., Ltd

  • E-mail

    1234065@qq.com

  • Phone

    17749779099

  • Address

    2392A, 1st Floor, 199 Shiyi Road, Baoshan District, Shanghai

Contact Now
Function Description of EOCR-DG Protector
Date: 2025-11-28Read: 0

Overview of EOCR-DG

built-inMCU(microprocessor control unit)

overcurrent/phase loss/Reverse phase/unbalanced/locked-rotor/Ground fault protection

Adopting residual current detection methodGround fault protection

Wide current setting range

Automatic calculation of startup delay time

Display of Action Status and Reason

Timed action characteristic

Manual reset/Electrical (remote) reset

Excellent environmental tolerance

Ultra low power design

No voltage release function(No Volt Release / Fail-safeRunning)Ntype

DG: Core type,DGTTerminal block type

EOCR-DG (T) protection function

Overcurrent (O-Time)

Phase loss (within 4 seconds)

Reverse phase (0.1 seconds)

Unbalance (8 seconds)

Blocked rotation (after D-TIME, when I>Is × 3)

Grounding (0.5 seconds)

EOCR-DG (T) rated specifications

Product Information

brand

Schneider

product scope

EOCR

place of origin

Schneider Electric's Yishan Factory in South Korea

General agent in China

Shanghai Hanshi Electric Automation Equipment Co., Ltd

name

EOCR-DG (T) motor protection relay

model

EOCRDG-05RB,EOCRDG-05RM7,

EOCRDG-30RM7,EOCRDG-30NM7,

EOCRDGT-05RM7,EOCRDGT-30RM7

protection function

Overload: In>overcurrent setting value

phase loss protection

Ground fault (leakage): Ig>Ground current set value

Reverse phase protection

Unbalance protection: 50%

Blocked rotor during startup: In>3 times the overcurrent setting value

Current setting range

Type 05: 0.5-6A leakage current 0.5-2A

Type 30: 3.0-30A leakage current 0.1-5 A

30-600: Used in conjunction with the 05 type external CT, with a leakage current of 0.5-2 A

operating power supply

B:AC/DC 24V

M7:AC 220V

frequency

50/60Hz

Installation Method

Installation of EOCR-DG panel

EOCR-DGT 35 mm DIN rail/panel installation

Electrical/mechanical characteristics

Contact type and configuration

1 NC + 1 NO OL)

Reset method

Manual reset

Electrical reset: 0-1 second

Time Setting

Start delay time: 60-4 × (I/Is), up to 60 seconds

Overcurrent action time: 0.2-15 seconds

Ground fault action time: 0.5 seconds

Action display

5 LED

Relay power consumption

2W

[Ue]Rated working voltage

690 V AC 50... 60 Hz main circuit complies with CSA

690 V AC 50... 60 Hz main circuit complies with IEC 60947-4-1

600 V AC 50... 60 Hz main circuit complies with U

[Applause]Rated pulse withstand voltage

6 kV complies with IEC 60947-4-1

[Ith]continuous current

5A control circuit

allow current

250 V, 5 A AC

Wiring specifications

Control circuit (ear clip wiring): 2 × 1... 2.5 mm ² flexible wire (without cold pressed end), screw M3.5

Control circuit (ordinary wiring): 2 × 1... 2.5 mm ² flexible wire (without cold pressed end), screw M3.5

Control circuit (with terminal wiring): 2 × 1... 2.5 mm ² flexible wire (with cold pressed terminal), screw M3.5

Tightening torque

Tightening torque of control circuit terminal: 1.7 N · m (suitable for ear clip or cable, screw head width 7 mm)

Product dimensions

DG width 90 mm x height 40 mm x depth 91 mm

DGT width 90 mm x height 81 mm x depth 91 mm

Product weight

DG 0.164kg

DGT 0.423kg

Usage environment

Operating Temperature

– 20 °C ~ + 60 °C

Storage temperature

– 30 °C ~ + 80 °C

Use altitude

2000 meters

IPgrade

IP20 complies with IEC 60529

Flame retardancy

650 ° C, compliant with IEC 60695-2-12

960 ° C, compliant with UL 94

impact resistance

15 gn,11 ms, 符合 IEC 60068-2-7

anti-vibration

4 gn (panel installation), compliant with IEC 60068-2-6

insulation withstand voltage

2 kV,50–60 Hz, Between the shell and the circuit, in accordance with IEC 60255-5

1 kV,50–60 Hz, Between contacts, in accordance with IEC 60255-5

2 kV,50–60 Hz, Internal circuits comply with IEC 60255-5

surge resistance

6 kV, Compliant with IEC 61000-4-5

Electromagnetic Compatibility (EMC)

Radio frequency electromagnetic field radiation immunity: 10 V/m, level 3, in compliance with IEC 61000-4-3

Electrostatic discharge immunity: 8 kV (air), 6 kV (contact), in accordance with IEC 61000-4-2

Fast transient/burst immunity: 2 kV, compliant with IEC 61000-4-4

RF conducted immunity: 10 V, compliant with EN 61000-4-6

RF conducted emission: Grade, compliant with EN 55011