485 communication cables are usually
485 communication cables are commonly used
shielded layerCommonly used are aluminum foil and woven mesh double shielding, or tin plated copper wire drainage ground wire, which effectively suppresses electromagnetic interference.
Grounding requirementsOrdinary shielded cables need to be grounded at one end, while armored cables need to be grounded at both ends.
Industrial environment: Recommend 18AWG or thicker wire diameter, double shielded cable.
Harsh environment (such as buried or explosion-proof): Armored cables (ASTP) are required.
Transmission distance: The standard is 4000 feet (about 1219 meters), but it can actually reach 3000 meters.
Node count: Supports up to 128 device connections.