explanationApplication and Testing Standards of High Current Generator
High current generatorProduct Features:
◆ It has grounding detection function and zero return detection function. The test can only be carried out after the grounding and zero return are determined, which is safe and reliable;
◆ Approximate current boosting algorithm, automatically timing the current after reaching the set target output current, and the motor automatically returns to zero after the timing ends;
When the output current exceeds the set upper limit, the motor automatically returns to zero and an audible and visual alarm occurs;
Adopting a combination of hardware and software anti-interference technology, with stable performance, strong anti-interference ability, and adaptability to harsh electromagnetic environments;
◆ Automatic error diagnosis, easy to detect and solve problems;
◆ Optional remote communication and door interlockingAlarm bell, open voltage verification interface, etc;
◆ The startup displays the company name, etc., which is beneficial for promoting and advertising the company brand;
The product has a small volume, light weight, reasonable structure, and is reliable and durable.
High current generatorUsage:
When conducting large current tests, correctly connect the working circuit according to the circuit diagram of this product. Choose the position of the large and small range switches according to the magnitude of the output current. First, return the regulator to zero, then press the start test button (green). At this point, hold the regulator handle and slowly rotate the regulator's handwheel clockwise while watching the ammeter until the desired current value is reached. Once the set value is reached, immediately turn the regulator handwheel counterclockwise back to zero, press the stop button, and cut off the power.
The current regulator is a dry-type high current generator produced by our company, equipped with an autotransformer to output voltage (i.e. the input voltage of the generator) and obtain different required high currents.
High current generatorMain performance indicators:
1. Input power supply: AC: 220V-2, 50Hz
2. Output current: AC: i000A.5V or 500A.IOV
3. Distortion of output current waveform: ≤ 5%
4.4.1/2 LCD digital display, range: O~i000A, resolution: 0.1A, accuracy: ± 0.5%
5. Operating environment: Temperature 10-40~C, relative humidity<80%
6. Volume: 402X232X245mm '
7. Weight: 30kg
Notes:
1. The TD and SA casings must be grounded, and personal accidents and safety measures should not be ignored due to low voltage operation.
2. The wire from the secondary of the current collector to the test port should not be too long, and the cross-sectional area should be sufficient (the current density can be considered as 6-8 A/mm2). The contact surface should be cleaned (it can be fine, otherwise the joint will heat up and the current may not reach the rated value).
3. Before starting work, check that the power supply (TD to SA lead) has sufficient capacity (SA-2K and SA-4K can be considered as 50A), otherwise the heating and voltage drop of the power supply line will affect the normal operation of AD903.
4. Both TD and SA casings must be grounded to ensure personal safety.
5. There should be no flammable materials on the work site. Sufficient fire extinguishing equipment should be prepared for long-term temperature rise tests.
6. Continuous heating test, there should be someone on duty on site. Regularly check the heating condition of the current source equipment, wires, and connectors, and keep records. Due to fluctuations in grid voltage, pay attention to adjusting TD to maintain the rated test current.
8. The experimental work should comply with the relevant provisions of the electrical safety work regulations and formulate practical safety measures.
Dear customer:
Thank you for your interest in our product. In addition to introducing this product, our company also hasVariable frequency series resonance,Series resonance test device,Variable frequency series resonant withstand voltage test device,Transformer oil withstand voltage tester,High voltage insulation pad、Short circuit grounding wire、Relay protection tester、High voltage nuclear phase analyzerIf you are interested in our products, please feel free to inquire. Thank you!