What is an explosion-proof sound and light alarm light? How to choose explosion-proof sound and light alarm?
Date: 2023-06-10Read: 7

Explosion proof sound and light alarm "is an alarm signal device that sends warning signals to people through sound and various lights, and does not ignite flammable and explosive gases. When an accident or fire occurs on the production site, the control signal sent by the fire alarm controller activates the sound and light alarm circuit, emitting sound and light alarm signals to achieve the alarm purpose.

Product Introduction

Explosion proof sound and light alarm lamp is a small sound and light alarm device suitable for hazardous areas in Zone 1 and Zone 2, as well as explosive gas environments of Class 11A, IIB, IIC, and temperature groups T1-T6.

The product adopts a stainless steel shell and a red PC lampshade, with high strength, impact resistance, and high explosion-proof rating; The LED light-emitting tube used has the characteristics of high brightness, long lifespan, and maintenance free; At the same time, the widely used G3/4 "pipe thread (external) electrical interface design makes it easier to connect to other devices to achieve sound and light alarms in hazardous areas.

This product also uses * * noise reduction control design. When used in conjunction with gas detectors, noise reduction control can be achieved through a remote control calibrated with the detector. After noise reduction, the light alarm still remains, making it easy to operate and use.

The sound and light alarm adopts a dedicated integrated circuit design, which works stably and has a long service life. It uses high brightness light-emitting diodes inside, which are clear and visible from multiple angles. It has the advantages of small size, loud sound, light weight, and easy installation.

The design, manufacturing, and inspection of the product comply with enterprise standards and provide explosion-proof certification qualifications. This sound and light alarm can be used in conjunction with gas detectors and alarms with node outputs.

637813783165738362171.jpg


Technical parameters:

Working voltage: 15VDC~30VDC;

Alarm sound:>85dB;

Working temperature: (-40~55) ℃;

Explosion proof type: ExdIICT6;

Alarm frequency: 0.5Hz/3Hz;

Interface size: M20'1.5;

Rated power:<1.5W;

Lifespan: Continuous alarm for less than 5 hours, with a service life of 3 years;

Alarm method: sound and light alarm;

Environmental temperature: -25~+40 ℃;

Environmental humidity:<90% RH;

Material: Die cast aluminum;

Connection thread of outlet hole: G3/4 'pipe thread (external);

Product installation:

The explosion-proof sound and light alarm is directly driven by DC24V. If the installation cable length is not enough, an explosion-proof junction box should be used for expansion during installation. The installation location can be chosen near the door or in a place where people often go out and are clearly visible. A height of 1.6-2.2 meters is recommended.

This sound and light alarm can be used in conjunction with gas detectors and alarms with node outputs.

Before wiring, please power off the detector or alarm, connect the black power line (black line: negative terminal) of the sound and light alarm to the negative terminal of the detector or alarm, string the red power line (red line: 24V) of the sound and light alarm into the node output, and connect the other end of the node output to the DC24V terminal of the detector or alarm.

637813783452385194292.jpg


Usage:

1. This sound and light alarm can be used in conjunction with gas detectors and gas alarms with node outputs. 2. Before wiring, please turn off the power of the detector or alarm, connect the two power lines (blue line: negative) of the sound and light alarm to the negative terminal of the detector or alarm, string them into the node output (red line: DC24V), and connect the other end of the node output to the DC24V terminal of the detector or alarm. Note 1: To ensure safe use, please strictly follow the instructions for use

2When an alarm occurs on site, please handle it promptly to avoid the sound and light alarm being in continuous operation for a long time and shorten its service life.

3. It is strictly prohibited to dismantle with electricity in flammable and explosive places. Do not damage the explosion-proof surface during installation and keep it clean. The fastening screws of the explosion-proof surface should be tightened evenly, and attention should be paid to not containing wires or other foreign objects on the explosion-proof surface.

4. The control line should be laid separately from the strong electromagnetic field conductor. If it cannot be avoided, the detection bus cable should use armored cable with shielded wire, and ensure that the shielded wire is well grounded. Long term use requires regular testing of the explosion-proof sound and light alarm to ensure its performance is intact. If it fails or is damaged, it should be repaired by professional personnel.