Characteristics and advantages of HYDR transformer short-circuit impedance testerSelection Reference
1. Measurement of short-circuit impedance: Used for low-voltage short-circuit impedance experiments of transformers, it can display measurement parameters such as voltage, current, active power, impedance value, impedance voltage percentage, reactance value, leakage inductance value, etc. in three-phase or single-phase on the same screen;
2. Measurement of no-load loss: The instrument displays the three-phase voltage, three-phase current, and three-phase power. The instrument displays the distortion rate of the applied power waveform and calculates the percentage of no-load current and no-load loss of the transformer;
3. Measurement of load loss: displays three-phase voltage, three-phase current, and three-phase power, automatically calculates the impedance voltage percentage of the transformer, converts it to load loss at rated temperature and rated current, and the instrument has frequency conversion function, which can accurately measure over a wide frequency range;
4. Phase separation measurement: used to check for defects in single-phase windings of three-phase transformers or situations where there is no three-phase power supply on site. The phase separation test uses a single-phase power supply, and after measuring each single-phase data separately, it can be automatically converted into three-phase parameters;
5. Measurement of zero sequence impedance: The measurement of zero sequence impedance is suitable for transformers with star connections and neutral points on the high voltage side. The instrument can record zero sequence impedance, zero sequence reactance, zero sequence inductance, impedance angle, and zero sequence resistance;
6. The instrument has harmonic analysis function, which can measure the content and total distortion rate of multiple harmonics, and has original waveform and bar chart display;
7. The instrument has a large screen LCD display that can display three-phase voltage, three-phase current, three-phase power, three-phase impedance value, three-phase impedance voltage percentage, three-phase reactance value, three-phase leakage inductance value, three-phase average voltage, average current, three-phase total power, and related data on the same screen. The instrument adopts a Chinese menu, Chinese prompts, and simple operation;
8. The instrument is equipped with a USB interface, which allows the data stored in the instrument to be imported into the USB at any time. During instrument testing, it can be directly stored on the USB;
9. Built in memory, not lost in case of power failure, the instrument can store 400 sets of data;
11. The system comes with a printer that can print test data and memory browsing data;
12. Permanent calendar and clock functions, capable of time calibration;