Product Overview
DFTC-HW(K)Explosion proof infrared beam smoke and fire detector(Hereinafter referred to as detector)It is a flameproof reflective linear infrared beam smoke detector. This detector can be equipped with a coded linear beam smoke and fire detector produced by the host manufacturer. The detector must be used in conjunction with a reflector, but one or four reflectors may be used depending on the installation distance between the two. The explosion-proof performance of the detector meets the requirementsGB3836—2000 According to the requirements of the series standards, the inspection unit has passed the inspection and obtained the explosion-proof certificate. Applicable to1 District2 The area contains Class IIATheBTheClevelT1~T6Hazardous locations in explosive gas environments with temperature groups.
DC24V Explosion proof Linear Infrared Beam Smoke and Fire Detector
Performance Characteristics
1. Communication method: non-polar dual bus; And relay output andRS485outputmodbusagreement
2. Equipped with automatic compensation function, it can automatically compensate for the impact caused by factors such as dust and vibration to a certain extent, improving the performance
Reliability of detectors;
3. Easy debugging, with concentric laser module indication, making it easy to find the optical path, and digital display to indicate the reflected light intensity;
4. Sensitivity and distance values can be set on-site through a handheld encoder;
5. PCBFully sealed protection process for the board.
6.Supports both encoding and non encoding application modes.
Product Parameters
1. Explosion-proof marking:ExdⅡCT6 Gb
2. Power supply voltage:DC15V~DC28V
3. Power supply current:Debugging current ≤20mA;
Monitoring current ≤12mA;
Alarm current ≤22mA
4. Usage environment:Temperature: -20℃~+50℃
Relative humidity: ≤95%Non condensing atmospheric pressure:80kPa~110kPa
5.Indicator lights: Debugging status: Green and yellow indicator lights light up and flash in a specific way;
Normal monitoring status: The red indicator light flashes periodically;
Fire alarm status: The red indicator light is always on, and the yellow indicator light is off;
Fault status: The yellow indicator light is constantly on;
The light path is completely blocked: the detector first reports a fault and lights up the yellow indicator light,20sThe rear detector will report a fire alarm again, and
Turn on the red indicator light and turn off the yellow indicator light.
6. Fire alarm and fault contact output (invalid output terminal when encoding mode):
Fire alarm relay: contact capacity30V/2A, normal wiring terminalHJ1TheHJ2Normally open, closed in case of fire alarm.
Fault relay: contact capacity30V/2A, normal wiring terminalGZ1TheGZ2Normally open, closed in fault state.
7.Protection area: The maximum protection area of the detector is100m×14m=1400m 2 ,maximum width14m
8Sensitivity level: Total 3 level
First level sensitivity: highest sensitivity
Secondary sensitivity: moderate sensitivity
Level 3 sensitivity: low sensitivity
9. Thread of outlet:2-G3/4
10.Installation size:2-φ 11, center distance284mm