Product Name: |
Temperature and humidity transmitter |
|
Product model: |
BTH-6S-L350 |
|
edition: |
V1.0 |
|
Developed by: |
He Genwen |
|
Reviewer: |
Yuan Chao |
BTH-6S-L350 is a high-performance temperature data acquisition transmitter that uses the MODBUS industrial control bus protocol. It can be connected to multiple transmitters in a common bus network or to other bus networks that comply with the MODBUS RTU protocol. Real time and stable monitoring of changes in temperature and humidity environment. This product has the characteristics of good waterproof performance, easy installation, reliable sensor performance, long service life, and fast response speed.
Communication, warehousing, tobacco, pharmaceutical and other industries; Communication base stations, temperature and humidity meters, humidification equipment, dehumidification equipment, high-end air conditioning and other products.
|
Working power supply |
DC5~24V |
|
output signal |
MODBUS RTU protocol |
|
Temperature measurement range |
-40~80℃ |
|
Humidity measurement range |
0~ 100%RH |
|
Temperature measurement accuracy |
± 0.5 ℃ (@ 25 ℃), ± 1 ℃ (full range) |
|
Humidity measurement accuracy |
± 3% RH (@ 25 ℃), ± 5% RH (full range) |
|
response time |
<15S(25℃) |
|
operation temperature |
-40℃~80℃ |
|
storage temperature |
-40℃~80℃ |
|
casing |
100mm * 16mm * 16mm (length * width * height) |

1. Positive pole of power supply (VCC)
2. RS485 output A
3. RS485 output B
4. Negative pole of power supply (GND)

1. Before connecting the power supply, please confirm if the wire sequence is correct;
2. Do not install the transmitter when the temperature exceeds the working range;
3. The transmitter should be installed in a location that can effectively reflect the temperature of the measured area, and should be kept away from heat or cold sources;
4. Construction personnel should wear anti-static gloves and cut off power during installation and wiring, and should not operate with live electricity;
5. If there is a significant temperature difference between the installation surface and the tested environment, it is recommended to use a bracket with a distance of 20CM for installation;
6. Some technical indicators of the product may be modified, and the indicators on the product label shall prevail.
Within 12 months after the product leaves the factory, free repair services will be provided based on normal use and non-human damage.