-
E-mail
441955402@qq.com
-
Phone
13175671188
-
Address
Room 910, 9th Floor, Building 2, No. 64 Tiancheng Road, Shangcheng District, Hangzhou City, Zhejiang Province
Hangzhou Hangrui Electric Power Automation Co., Ltd
441955402@qq.com
13175671188
Room 910, 9th Floor, Building 2, No. 64 Tiancheng Road, Shangcheng District, Hangzhou City, Zhejiang Province
Nanjing Nanrui Jibao RCS9611CS Line Protection Measurement and Control Device
For example, if GL1 needs to act on outlet trip relay 1, then cross handle 1 in the column where GL1 is located and in the row where CK1 is located.
If I01 and I02 also need to act on the outlet trip relay 1, then cross handle the column where I01 and I02 are located and the row where CK1 is located
Thus, in line CK1, a 16 bit binary bit string can be obtained:
CK1=0000000011000001
If a certain set of exports is not used, such as CK3, it can be completely rounded to 0, that is: 0000000000000000.
Enter the above binary bit strings for CK1, CK2, CK3, and CK4 in the protection setting menu to complete the jump
Setting of gate mode.
2.13 Device self-test
When the device detects a hardware malfunction, it sends a device lockout signal and locks the device (BSJ relay returns).
Hardware failures include: setting error, RAM failure, ROM failure, power failure, outlet circuit failure, CPLD failure.
2.14 Device operation alarm
When the device detects the following conditions, it sends an abnormal operation signal (BJJ relay action):
TWJ abnormality, line voltage alarm, frequency abnormality, PT disconnection, control circuit disconnection, grounding alarm, overload
Alarm, zero sequence segment III alarm, spring not storing energy, CT disconnection, overvoltage alarm, zero sequence overvoltage alarm.
2.15 Remote control, telemetry, and remote signaling functions
There are three main types of remote control functions: normal remote control tripping, normal remote control closing, and grounding line selection remote control tripping and closing. standard
Configure only one set of remote control output contacts (fixed corresponding to this switch); Two additional remote controls can be provided as an optional option
Refer to Sections 5.4, 5.1, and 5.2.
Remote measurement includes Iam, Icm, I0, UA, UB, UC, UAB, UBC, UCA, U0, F, P, Q, COS ф
14 analog quantities. The active and reactive energy are calculated through integration, and all of these quantities are calculated in real-time locally,
Real time accumulation. The current accuracy reaches 0.2 level, and the rest of the accuracy reaches 0.5 level.
The remote signaling volume mainly includes 16 custom remote signaling inputs and event sequence records (SOE). Remote signaling resolution is less than
1ms。
2.16 Time synchronization function
The device has software timing and hardware timing functions. Hardware timing is either second pulse timing or IRIG-B code timing,
Automatic device recognition. The time interface adopts an average 485 differential level, corresponding to terminals 207-209.
When the device detects a hardware timing signal, a "·" will be displayed in the upper right corner of the LCD main interface.
Nanjing Nanrui Jibao RCS9611CS Line Protection Measurement and Control Device
3.3.1 Analog Input
The external current and voltage input are isolated and transformed by an isolation transformer, and then input to the analog-to-digital converter through a low-pass filter,
After sampling and digital processing, the CPU forms various protective relays.
IA, IB, and IC are three-phase current inputs for protection purposes.
NARI-RELAYS RCS-9611CS Line Protection Measurement and Control Device Manual
I0 is the zero sequence current input. It can be used for zero sequence overcurrent protection (alarm or trip), as well as for small current grounding
Used for route selection. When zero sequence current is used for small current grounding line selection, it is required to input from a dedicated zero sequence current transformer.
Iam and Icm are measurement currents that need to be input from a dedicated measurement CT to ensure sufficient accuracy in remote measurement.
UA, UB, and UC are bus voltages, which are shared for protection and measurement in this device. They are measured together with Iam and Icm
Calculate the P, Q, COS ф, kWh, and kVarh of the cost line. If there is no corresponding bus PT or the power used by this device
If voltage is not involved, UA, UB, and UC can be disconnected. To prevent the device from sending PT disconnection signals, simply adjust the protection settings
The control word 'PT disconnection detection input' exits.
UX is the line voltage, which is used for detecting no voltage in the reclosing circuit and detecting synchronization. It can be 100V or 57.7V,
Just need to be consistent with the "rated secondary value of line PT" in the system settings. If the reclosing is not activated or the reclosing is not adopted
The inspection method, UX can be disconnected.
This device produces 3U0 and is used for zero sequence voltage alarm judgment and zero sequence voltage measurement.
3.3.2 Backboard wiring instructions
Terminal 401 is the input terminal for the remote control positive power supply. Only when it is connected to the positive power supply will the device perform remote jumping, remote closing, and selection
The line function and remote modification of the soft pressure plate function are activated, and it also serves as the remote tripping outlet (413) and remote closing outlet (412)
The public end.
Terminal 402 is the control positive power input terminal, and it is also the protection trip outlet (414) and the protection closing outlet
The public end of (415).
Terminals 404-405 are the idle contacts for the total output of the accident.
Terminals 406-407 are KKJ (closed position) output empty contacts.
Terminal 408 is the protective closing entrance.
Terminal 409 is the protection trip inlet.
Terminal 410 is the manual closing entrance.
Terminal 411 is the manual trip inlet.
Terminal 412 is the remote closing outlet (YHJ), which can be connected to terminal 410 through a pressure plate or directly.
Terminal 413 is the remote tripping outlet (YTJ), which can be connected to terminal 411 through a pressure plate or directly.
Terminal 414 is a protection trip outlet 1 (BTJ) and can be connected to terminal 409 through a pressure plate.
Terminal 415 is the protective closing outlet (BHJ) and can be connected to terminal 408 through a pressure plate.
Terminal 416 is connected to the circuit breaker trip coil.
Terminal 417 is the negative terminal of the closing monitoring relay.
Terminal 418 is connected to the circuit breaker closing coil.
Terminal 419 is the negative terminal of the jump monitoring relay.
Terminal 420 is the control negative power input terminal.
Terminals 421-426 are signal output idle contacts, with 421 being the common terminal.
Terminal 422 corresponds to the locking signal output of the device.
Terminal 423 corresponds to the device alarm signal output.
Terminal 424 corresponds to the output of the protection trip signal, which can be selected through a jumper whether to hold or not (default is not to hold at the factory).
Terminal 425 corresponds to the protection closing signal output, which can be selected by jumper to maintain (default is non maintained at the factory).
Terminal 426 corresponds to the disconnected output of the control circuit.
Terminals 427-428 are defined as protection trip outlet 2 (TJ).
Terminals 429-430 are defined as trip position (TWJ) contacts.
Terminal 301 is for protecting the power supply ground. The terminal is connected to the grounding terminal on the bottom right of the back of the device and then connected to the substation grounding network
Reliable connection.
