E-mail
1234065@qq.com
-
Phone
17749779099
-
Address
2392A, 1st Floor, 199 Shiyi Road, Baoshan District, Shanghai
Shanghai Hanshi Electric Automation Equipment Co., Ltd
1234065@qq.com
17749779099
2392A, 1st Floor, 199 Shiyi Road, Baoshan District, Shanghai
Product information of EOCRDZ Schneider leakage protector
Overview of EOCR-DZ
✔ Built in MCU (microprocessor control unit)
✔ Overcurrent/phase loss/reverse phase/imbalance/locked rotor/grounding protection
✔ Grounding protection using zero sequence current detection method
✔ Wide current setting range
✔ Start automatic calculation of delay time
✔ Action and Reason Display
✔ Timed action characteristic
✔ Manual (immediate)/electric (remote) reset
✔ Strong environmental resistance
✔ Super energy-saving type
✔ No voltage release function/fail safe action → N-type
✔ DZ: through type, DZT: terminal type
EOCR-DZ (T) protection function
✔ Overcurrent (O-TIME)
✔Phase loss (within 4 seconds)
✔Reverse phase (0.1 seconds)
✔Unbalance (8 seconds)
✔Blocked rotation (after D-TIME, when I>Is × 3)
EOCR-DZ (T) rated specifications
Product Information | |
brand |
Schneider |
product scope |
EOCR |
place of origin |
Schneider Electric's Yishan Factory in South Korea |
General agent in China |
Shanghai Hanshi Electric Automation Equipment Co., Ltd |
name |
EOCR-DZ(T)Motor protection relay |
model |
EOCRDZ-05RF7, EOCRDZ-05NF7,EOCRDZ-05RM7, EOCRDZ-10RF7,EOCRDZ-10RM7,EOCRDZ-10NM7, EOCRDZ-60RF7,EOCRDZ-60RM7,EOCRDZ-60NM7, EOCRDZT-05RM7,EOCRDZT-60RM7 |
protection function |
Overload: In>overcurrent setting value phase loss protection Ground fault (leakage): Ig>Ground current set value Reverse phase protection Unbalance protection: 50% Blocked rotor during startup: In>3 times the overcurrent setting value |
Current setting range |
05Type: 0.5-6A leakage current 0.05-0.8A 10Type: 1.0-30A leakage current 0.05-0.8A 60Type: 5-60A leakage current 0.05-0.8A 60-600Used in conjunction with the 05 type external CT, with a leakage current of 0.05-0.8A |
operating power supply |
B:AC/DC 24V F7:AC 110V M7:AC 220V |
frequency |
50/60Hz |
Installation method |
EOCR-DZpanel mounting EOCR-DZT 35 mm DINInstallation of rails/panels |
Electrical/mechanical characteristics | |
Contact type and configuration |
1 NC + 1 NO OL) |
reset method |
Manual reset Electrical reset: 0-1 second |
Time Setting |
Start delay time: 60− 4 × (I / Is) 60 s Overcurrent action time: 0.2-15 seconds Ground fault action time: 0.5 seconds |
Action display |
5 LED |
Relay power consumption |
2W |
[Ue]Rated working voltage |
690 V AC 50...60 HzThe main circuit complies with CSA 690 V AC 50...60 HzThe main circuit complies with IEC 60947-4-1 600 V AC 50...60 HzThe main circuit complies with U |
[Applause]Rated pulse withstand voltage |
6 kVCompliant with IEC 60947-4-1 |
[Ith]continuous current |
5Acontrol circuit |
Allow current |
250 V, 5 A AC |
Wiring specifications |
Control circuit (ear clip wiring): 2 × 1... 2.5 mm ² flexible wire (without cold pressed end), screw M3.5 Control circuit (ordinary wiring): 2 × 1... 2.5 mm ² flexible wire (without cold pressed end), screw M3.5 Control circuit (with terminal wiring): 2 × 1... 2.5 mm ² flexible wire (with cold pressed terminal), screw M3.5 |
tightening torque |
Tightening torque of control circuit terminal: 1.7 N · m (suitable for ear clip or cable, screw head width 7 mm) |
Product dimensions |
DZWidth 90mm x Height 40mm x Depth 91mm DZTWidth 90mm x Height 81mm x Depth 91mm |
Product weight |
DZ 0.164kg Weight 0.423kg |
Product information of EOCRDZ Schneider leakage protector

Schneider EOCRDZ/DZT series




Protection function: overcurrent, phase loss, reverse phase, imbalance, braking, grounding fault protection function
Shanghai Hanshi Electric, as the Chinese manufacturer of Schneider EOCR (formerly known as Sanhe) intelligent motor comprehensive protectors, has been providing long-term stable supply and sales of the full range of EOCR products, with quality assurance, and providing customers with good pre-sales, in sales, and after-sales services from beginning to end! The company has received unanimous recognition and praise from a large number of customers, and has maintained long-term strategic partnerships with well-known listed companies and large enterprises in the industry, establishing deep mutual trust and cooperation, and jointly promoting the rapid development of the industry.
EOCR, formerly known as Sanhe in South Korea, is a manufacturer of electronic relays. It was acquired by Schneider in 2001 and is now a wholly-owned subsidiary of Schneider. It is sold independently in China and is not sold in the same system as Schneider Electric in China. Shanghai Hanshi Electric is sold in China! For product selection and technical consultation, please contact us by phone/email/.